Input/Output: Inputs.
Internal I/O circuit common: PNP (– common).
I/O points: 8 points.
I/O connection method: Sensor connector.
Rated voltage for I/O power supply: 24 VDC.
Eight Waterproof Terminal Models.
Emphasizing Cost Efficiency.
Reduced Labor.
required for installation. No tools are required for,
connection to a variety of devices.
Reduced Wiring.
other devices.
Relay Box not Required.
mounting.
Easier Maintenance.
maintenance time.
Compact design (160 x 54 mm (W x H)) (8-point models).
the switch and connectors on the front side of the Terminal.
System Configuration.
Specifications: Inputs; PNP (- common); 16 points.
I/O connections: M3 Screw terminals.
Rated internal circuit power supply voltage:
Supplied from the communications connector.
Rated I/O power supply voltage: 24 VDC.
Allows I/O Expansion with Transistor Terminals.
Wide variety of data, such as maintenance system data,
can be collected without affecting the productivity,
of the control system OMRON SRT2-ID08CL-1
SRT2-ID08CL-1
Valuable information can be collected,
and managed through the network, including information,
on the communications power supply.
voltage levels, Unit wear and tear,
and equipment operating information.
Expansion via Expansion I/O Units.
With no communications baud rate settings,
required and detachable terminal blocks,
maintenance is easier OMRON SRT2-ID08CL-1. EtherCAT-compatible encoder input terminal which,
enables high-speed and accurate control.
Two counter function available.
Pulse count within 32 bit range.
Maximum input pulse frequency of 4MHz,
(Line driver input after quadrature).
High-speed network EtherCAT enables,
high-speed and accurate control.
Selectable two input types:
Open collector input and line driver input OMRON SRT2-ID08CL-1.
Built-in two external latch inputs,
and one reset input.
Selectable node address settings: setting with,
rotary switches and setting on tool software.
Detachable screw terminal will facilitate,
the maintenance work SRT2-ID08CL-1 OMRON. Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min. (between each in,
put terminal and the G terminal) SRT2-ID08CL-1 OMRON.
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms SRT2-ID08CL-1 OMRON.
(Default setting: 1ms)
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common terminal is provided for,
each connector SRT2-ID08CL-1.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software OMRON SRT2-ID08CL-1.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.