How many analog modules Q4MCA-2MBS can the FX series PLC take
Time: 1/31/2018 10:48:49 AM

Excuse meseries Q4MCA-2MBS PLC Q4MCA-2MBS can bring 4 FX-4AD+FX-4DA at the same time, a total of 8, if it can be brought, how to input and output performance and how to react.
Re:   Time: 2/1/2018 2:11:00 AM
What type of PLC do you use, please? In addition, is the above FX-4AD and FX-4DA mean FX2N-4AD and FX2N-4DA?
Re:Re:   Time: 2/1/2018 4:35:00 AM
PLC is FX2N-128MR and FX2N-4AD and FX2N-4DA
Re:Re:Re:   Time: 2/1/2018 9:23:00 AM
PLC is FX2N-128MR and FX2N-4AD and FX2N-4DA
Re:Re:Re:Re:   Time: 2/1/2018 11:47:00 AM
FX2N-128MR can bring 4 FX2N-4AD and 4 FX2N-4DA, and do not violate the selection rules.