Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) .
ON delay: 0.1 ms max.
OFF delay: 0 D2F-FL3-D. 2 ms max.
Input filter value: Without filter, 0
D2F-FL3-D5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point D2F-FL3-D.
Unit power supply current consumption: 230 mA max .
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors D2F-FL3-D.
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. UM: 31.2K words.
DM: 6K words.
EM: 6Kx3 banks(18K) words.
Instruction processing time (basic instructions): 0.1 µ.s min.
No. of I/O points: 1, 184 points.
Max. no.of con-necting Expansion I/O Racks: 3 Racks.
Max. no. of connecting High-density I/O Units(i.e., Group-2): Unavailable.
Max. no. of con-necting Special I/O Units: 10.
RS-232C: NO.Classification: High-sensitivity.
Contact gap: H (0.25 mm).
Actuator: Panel mount cross roller plunger.
Best-selling Basic Switch Boasting D2F-FL3-D.
Hiigh Precision and Wide Variety .
A large switching capacity of 15 A with high repeat accuracy.
A wide range of variations in contact form for your selection: basic,
split-contact, maintained-contact, and adjustable contact gap types.
A series off sstandard models for micro loads is available D2F-FL3-D.
A series of molded terminal-type models incorporating safety,
terminal protective cover is available.
D2F-FL3-D Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=D2F-FL3-D&select=5