Input capacity: 32 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC) .
ON delay: 0.1 ms max.
OFF delay: 0 E5EC-RX4DSM-010. 2 ms max.
Input filter value: Without filter, 0
E5EC-RX4DSM-0105 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 32 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point E5EC-RX4DSM-010.
Unit power supply current consumption: 230 mA max .
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 220 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary E5EC-RX4DSM-010.
Digital I/O terminal with industry,
standard e-CON connectors .
A common terminal is provided for,
each connector.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance. Actuator: Adjustable roller lever, form lock (metal lever, resin roller).
Conduit size: 1-conduit; G1/2.
Built-in switch mechanism: 1NC/1NO (Slow-action).
A Series of Pull-reset Models Now.
Available.
Lineeup includes three coontact models with 2NC/1NO and 3NC,
contact forms in addition to the previous contact forms 1NC/1NO and 2NC E5EC-RX4DSM-010.
M12-connector models are available, saving on labor and,
simplifying replacement.
Standardized gold-clad contacts provide high contact reeliability E5EC-RX4DSM-010.
Can be used with both standard loads and microloads.
Conforms to EN115, EN81-1 and EN81-2.
Certified standards: UL, EN (TÜV), and CCC.
E5EC-RX4DSM-010 Operation manual/Instructions/Model selection sample download link:
/searchDownload.html?Search=E5EC-RX4DSM-010&select=5