Input signal: platinum temperature resistance 3 wire 4 points.
Sensor current: 1mA.
Applicable PLC:FX1N, FX2N, FX3U, FX2NC (to FX2NC-CNV-IF).
Applicable PLC:FX3UC (to FX2NC-CNV-IF or FX3UC-1PS-5V).
PT type temperature sensor input module.
Platinum temperature measurement resistor (Pt100 3 wire) temperature sensor input module .
4 channels can be entered A1SX41-S2.
Unit can be set to Celsius or fahrenheit.
Resolution is 0
A1SX41-S22~0.3 degree of high precision. Input: 4 channels.
Thermocouple (K, J, T, B, S, E, R, N, U, L, PLlI, W5Re/W26Re,,).
No heater disconnection detection function.
Sampling period: 0.5s/4 channel.
18 point terminal station.
Peak current suppression.
Can prevent the simultaneous opening of the output to control the peak current, which is helpful for saving energy and reducing the operation cost A1SX41-S2.
Heating function at the same time.
The multiple loop can reach the set value at the same time to carry out the uniform temperature control,
Helps to prevent no-load and effective energy saving and reduce operating costs.
Automatic adjustment function.
The PID constant can be adjusted automatically in the control process A1SX41-S2.
Automatic adjustment of cost (time, material and electrical energy) can be reduced.
Can be flexible in various settings, to achieve the best temperature control of the temperature control module.
Equipment for high temperature control stability of extrusion molding machine,
The temperature regulating module has the function of preventing overheating and preventing over cooling.
According to the control object device, select the standard control (heating or cooling) or the heating and cooling control (heating and cooling) mode.
In addition, the mixed control mode (combined with the standard control and heating - cooling control) can be selected. Output type: transistor output, drain type.
Output points: 4 points.
OFF leakage current: 0.1mA.
Outputt protection function: No A1SX41-S2.
Rated load voltage / current: DC12V/DC24V/0 .1A.
External connection: 2 wire.
Screw terminal table type.
Minimum size of industry.
The connection object at a glance with terminal cover plate.
Input module for public end of positive pole and negativve pole A1SX41-S2.
Terminal table structure capable of connecting with 2 wire type sensor and load in the same condition.
Can be installed along the 6 direction.
A1SX41-S2 Operation manual/Instructions/Model selection sample download link: