LK Automation Limited LK Automation Limited
Problem sort: OMRON | MITSUBISHI | Proface | Mennekes | Yaskawa
Home >> Problems
The maximum speed that the motor Q02UCPU can operate is very different from the rated speed
Time: 7/16/2017 4:12:42 PM

MR-J2S-10nnecting Q02UCPU the Q02UCPU motor of type HC-MFS1
Connect via PCI-7344 card and SCB-68 and controller. When using the software Measurement Automation to drive the motor, the motor has been unable to reach the highest rated 3000r/min.
At Measurement, Automation input speed, acceleration and other values, the speed that can now be achieved is not even half as high as the top speed
Re:   Time: 7/17/2017 2:32:00 AM
AL.35 alarm is the input pulse, the input frequency is too high.
Thank you