MITSUBISHI FR-D700 frequency converter FR-D740-0.4K-CHT how to set external start and external analog control
Time: 11/20/2017 11:14:56 AM

Hello! Consulting FR-D740-0.4K-CHT how FR-D740-0.4K-CHT to set frequency converter FR-D700 frequency converter: 1, frequency converter for external start 2, inverter for external analog 0-10V control
Please inform the detailed steps of setting!!
Thank you
Re:   Time: 11/21/2017 2:02:00 AM
Hello. Set Pr73=0, Pr79=2, can be given by the external STF-SD positive turn start, analog frequency modulation.