LK Automation Limited LK Automation Limited
Problem sort: OMRON | MITSUBISHI | Proface | Mennekes | Yaskawa
Home >> Problems
GXWORK2 Q00CPU
Time: 7/4/2017 12:32:07 PM

When readhe Q00CPU Q Q00CPU series PLC program with GXWORK2, it is indicated that the configuration parameters of the current project and the intelligent function module are different. The starting XY address under the current project status is 00D0, the model is QD75MH1, the intelligent function module parameter starts, the XY address is 0040, and the model is reserved module. Will it cause problems for the PLC program? How to fix it?
Re:   Time: 7/5/2017 4:44:00 AM
Hello, this will affect the program, if you address the positioning module now is 00D0 if you want to re build a smart module, the initial IO to 00D0, the program inside the original 0040 address corresponding to the program will be converted into 00D0. Thanks for asking questions.
Welcome to call 400-- free technical hotline, get into Step by step technical letter
Related problems
Related products
MITSUBISHI
Basic type CPU
Q00CPU
MITSUBISHI Basic type CPU Q00CPU
Program capacity: 8K step. Input / outpu
Related download