PLC selecG-60MR, FX2N-2AD there FX2N-2AD is a weight sensor access FX2N-2AD, 3G programming manual contains instructions on the WR3A, FX2N-2AD, RD3A, but there is no comprehensive example, the 2AD manual does not have 3 series PLC programming examples. Is this written to enable data conversion?
WR3A K0 K21 H002 starts the analog-to-digital conversion of channel 1
The RD3A K0 K21 D0 saves the data to D0
Please advise. Thank you
Re: Time: 6/26/2017 3:05:00 AM
FX2N-2AD not FX3G-60MR use FX3G-60MR WR3A instructions, and the RD3A command is fine.